How do I connect in the measuring tubes for flow control in the fan chamber?

The measuring tubes must measure across the fan. This means that the negative tube, which is permanently fitted to the cone, must be routed out and fitted in the pressure sensor (not supplied). The positive tube should measure from the fan wall closest to the heat exchanger (SD exception) into the pressure sensor.