You might want to visit our global site:

AFL

Radial flow diffuser for supply air
  • Easily integrated to suspended metal ceiling systems
  • Suitable for room heights of 2.5–4 m
  • Suitable for high supply air temperature differences
  • Available with perforated front panel for a seamless visual integration with the ceiling design
  • Air distribution pattern can be blanked off using cover plates
  • Can be combined with commissioning box with a horizontal duct connection
  • Standard colour Jet Black RAL 9005
AFL with Q
SizeLPA = 25 dBLPA = 30 dBLPA = 35 dBLPA = 40 dB
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
20010035117481366515889
25014832170431965822679
35022325256342924533459
45032419372264283549347
55045118516235913167640
AFL with Q1
SizeLPA = 25 dBLPA = 30 dBLPA = 35 dBLPA = 40 dB
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
25013233151441745919479
35021425242332734330957
45030523345293913744248
55039121445275073557746
AFL with Q2
SizeLPA = 25 dBLPA = 30 dBLPA = 35 dBLPA = 40 dB
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
V
(m3/h)
∆p
(Pa)
2509933114431305614973
35016126182342074423458
45024022274283133735649
55030722350294013845849