Indoor Climate Product info in PDF form
 
Swegon Indoor Climate Systems 2004 - Air distribution products - Rev. 5 June. 2007
www.swegon.com
KSCb
Electronic carbon dioxide and
temperature sensor


FUNCTION
KSC is an electronic CO2 and temperature sensor which is used to control the ventilation requirement and heating/cooling of premises. KSC 1 has an integrated display that shows the current CO2 and temperature values.

QUICK FACTS
  • CO2 and temperature sensor for airing-cooling-heating
  • Also available for duct installation
  • Measurement range 0 - 2000 ppm CO2
  • Integrated display for CO2 and temperature values
  • Has three outputs for various applications
  • As an extra option there is a LONTALK® connection for communication with a master system or room regulator
  • Also available in a simpler version with CO2 only and without display, KSC 0 designed for the e.r.i.c. system


Figure 1.Placement of the sensor and room unit KSC.


DESIGN
KSC is a carbon dioxide sensor of the IR-type configured with an analogue 0-10 V DC output signal proportional to the CO2-content between 0-2000 ppm. Changes to the measurement range are possible using a computer connection or integrated push buttons. The sensor also features an integrated thermistor for temperature measuring, whose analogue signal can be combined with the CO2-signal. Normally only the CO2 -signal is used in the e.r.i.c. system. The relay output should only be connected to a 24 V AC supply that closes at C02 > 900 ppm and opens at C02 < 800 ppm.
KSC also has an output for heating via radiators. KSC is also available in a simpler version, type KSC 0, for CO2 measurements only. KSC is also available in a version with LONTALK® communications.


MATERIALS AND SURFACE TREATMENT
Enclosure of light beige plastic.

INSTALLATION (See figure 1)
KSC is ideally installed between 1.5 to 2 m above the floor on an optional non sunlit wall in the room. KSC 2, which is intended for duct installation, is fitted in the exhaust air duct as close to the room as possible.

COMMISSIONING
KSC 1 and 2 have pushbuttons that permit adjustment of the preset set values for temperature and C02 connected to OUT 1, 2 and 4. By using a special cable to connect to a computer running UIP software, all the set values can be adjusted and checked graphically. KSC 0 has fixed set values that cannot be changed.

MAINTENANCE
Dirty products may only be cleaned by wiping or vacuum cleaning. Further maintenance is not generally needed.

DECLARATIONS
The product is CE marked.
CE declaration and Environmental Product Declaration are available from our website.


CONNECTION
KSC is connected to a 24 V AC supply and is fuse protected with max 6 A. All other connections are made according to the wiring diagram for the product that KSC is to be connected to, see KCD, KCW, KRF or VAR. The outputs can be loaded with several actuators under the condition that the resulting load resistance is ³5kW.

Figure 2.Wiring diagram KSC.


Electrical data
Supply voltage
24V ±20% AC/DC

Power consumption

3VA
Ambient air temperature
0°C -+50°CC
Reaction time
2 min.

Humidity

0-95% RH (not condensing)
Enclosure class room installation
lP 20

Enclosure class duct installation

lP 65
Load on OUT1-4
>5kW
KSC 1 and 2
OUT1 0-10V DC
400-1000 ppm and p-band 23-25°C
OUT2 0-10V DC
0-2000 ppm
OUT4 heating control 0-10V DC
p-band 19-21°C
Relay
24 V AC max 0.5 A
KSC 0
OUT1 0-10V DC
0-2000 ppm
OUT2 2-10V DC
0-2000 ppm


Technical data
Diagram 1-3 shows the signal from temp and CO2 outputs, OUT 1 and 2. On OUT 4 p-band 19-21° applies.

Diagrams 1 and 2
Diagrams 1 and 2 show the actual value, the largest signal is the one placed on OUT 1, not applicable to KSC 0.


Diagram 3
Diagram 3 shows the CO2 value, in the 0-2000 ppm range, for the output that is normally used in the e.r.i.c. system. For KSC 1 and KSC 2 OUT 2. For KSC 0 OUT 1.


DIMENSIONS

Figure 3.Dimensions.


ORDER KEY

Product designation

Carbon dioxide

KSCb
-a

Model:
0 =room installation without display
1 = room installation
2 = duct installation

LONTALK® -design specified in clear text.


SPECIFICATION EXAMPLE
Swegons electronic carbon dioxide sensor type KSCb with following functions:
  • CO2-measurement
  • Temperature measurement
  • Airing - heating - cooling regulation
  • Integrated display
  • LONTALK® communications


Type:
KSCb 1
xx items


Registered design. The company reserves the right to make design changes without prior notice.


   

Swegon Worldwide
Austria Belgium Czech Republic Denmark Finland France Germany Hungary Italy Netherlands
Norway Poland Slovak Republic Spain Sweden Switzerland United Arab Emirates United Kingdom United States of America
Partners
Belarus Bosnia-Herzegovina Croatia Estonia Greece Iceland Israel Latvia Lithuania Portugal
Romania Russia Serbia Slovenia - air handling units Turkey Ukraine