Room unit for temperature


FUNCTION
KST is used in the e.r.i.c. system for individual control of the room temperature. All room units feature a temperature sensor this is affected by the temperature in the surrounding air and by radiant heat from the room. KST 2 and 4 variants have modular jacks for the connection of operator panel KOP which provides direct access to the regulator’s LonWorks-parameters. KST 1 is intended for the LonWorks-system with remote setting of the required room temperature.

QUICK FACTS
  • Temperature sensor of the thermistor type
  • Connecting the operator panel KOP
  • Adjustable set point value for the room temperature
  • Lockable setting range for the temperature
  • Available with a button for overtime work
  • Green running mode


Figure 1.Placement of the room unit KST.


DESIGN
KST is a temperature sensor this is affected by the temperature in the surrounding air and by radiant heat from the room. KST 2 and 4 variants have modular jacks for the connection of operator panel KOP and a LED with the following functions: Comfort mode =on, Standby =flashing, Shutoff = off. The functions are controlled by the regulator KCD, KCW or KRF, that KST is conntected to. There are further functions available depending on the type of room unit, e.g. bypass switch and set point value adjustment. The bypass button is only selected if a master control system sets the regulators in the different operating modes. KST 1 is selected for systems where only the room temperature is to be read on the regulator and where other functions are managed by a master system.

MATERIALS AND SURFACE TREATMENT
Manufactured in white and grey ABS-plastic.

INSTALLATION (See figure 1)
KST is ideally installed between 1.5 to 2 m above the floor on an optional wall in the room. Must not be exposed to direct sunlight.

MAINTENANCE
Dirty products may only be cleaned dusting or wiping with a damp cloth.

DECLARATIONS
The product is CE marked.
CE declaration and Environmental Product Declaration are available from our website.


CONNECTION
Connections are made according to the wiring diagram for the product that KST is to be connected to, see KCD, KCW or KRF.

Electrical data
Ambient temperature:
Operation
0°C -+50°C
Storage
-40°C -+70°C
Relative humidity
max 90% RH
(non condensing)
Enclosure:
Material
ABS-plastic
Enclosure class
lP 20
Sensor, thermistor
1800W at25°C
Accuracy, sensor, 0 to +35°C
±0,3°C
Time constant
approx. 7 min


KST variants
Variants
Temp.-
sensor
Operating
indicator
Bypass-
button
Set point
value setting
1
x
x
2
x
x
x
4
x
x
x
x


Figure 2.Design.


DIMENSIONS

Figure 3.Dimensions.


Wire cross-section requirements
Cable from room units max 30 m with 0.7 mm2. Connection to LONTALK® TP/FT-10 Free Topology Channel should be made using twisted pair cable. More information is avaible in our electrical guide that can be found on our website.

ORDER KEY

Product designation

Room unit

KSTb
-a

Variants:
1, 2 or 4
See table



SPECIFICATION EXAMPLE
Example of the specification text according to VVS AMA.GT XX
Swegon room unit for temperature control type KSTb which is included in the e.r.i.c. system, with the following functions:
  • Temperature sensor of the thermistor type
  • Connecting the operator panel KOP
  • Adjustable set point value for the room temperature
  • Lockable setting range
  • LED to indicate the operating mode


Type:
KSTb 2
xx st


Registered design. The company reserves the right to make design changes without prior notice.


   

Swegon Worldwide
Austria Belgium Czech Republic Denmark Finland France Germany Hungary Italy Netherlands
Norway Poland Slovak Republic Spain Sweden Switzerland United Arab Emirates United Kingdom United States of America
Partners
Belarus Bosnia-Herzegovina Croatia Estonia Greece Iceland Israel Latvia Lithuania Portugal
Romania Russia Serbia Slovenia - air handling units Turkey Ukraine