Indoor Climate Product info in PDF form
 
Swegon e.r.i.c. 2006, 25 April
www.swegon.se
KSPa
Electronic pressure sensor


FUNCTION
KSP is an electronic pressure sensor for the e.r.i.c. system. The pressure sensor is of the static type, i.e. there is no risk of fouling. KSP is available as a complete product for circular ducts and for surface mounting on rectangular ducts.

QUICK FACTS
  • Pressure measurement within 10-300 Pa
  • Static non fouling pressure measurement
  • Compact design for all installation instances
  • Available in sizes Ø160 to Ø500 and size dependent design for rectangular ducts


Figure 1.KSP for circular and rectangular ducts.


DESIGN (See figure 1)
KSP is available as standard in a circular design which is fully mounted on the unit via a sleeve fitted with a rubber seal against the duct system. In rectangular design, intended for assembly on the outside of rectangular ducts, the pressure sensor is mounted on a shelf with screw holes and equipped with a seal against the duct side.

MATERIALS AND SURFACE TREATMENT
All sheet metal parts are in galvanized sheet steel. All plastic parts are completely PVC free and are generally made of ABS-plastic.

INSTALLATION (See figures 2, 3 and 4)
KSP can be installed in any position in climate-conditioned areas. The diaphragm on the pressure sensor must always be mounted vertically. When installed horizontally the sensor position must be changed after installation. Electrical connection should be made according to the wiring diagram documented in the product section for KZP and KZM.
NOTE! The pressure sensor is supplied as standard for supply air systems. The pressure hose connection should be moved with installation in exhaust air systems, see figure 3.


MAINTENANCE
Dirty products may only be cleaned by wiping or vacuum cleaning.

DECLARATIONS
The product is CE marked.
CE declaration and Environmental Product Declaration are available from our website.


PLANNING
The pressure sensor is installed according to the recommendations in the planning guide located in the technical section. Demand on straight sections see figure 4.

Figure 2.Installation area requirements.


Figure 3.Installation.


Figure 4.Demand on straight sections before KSP.


CONNECTION
KSP is connected to a 24 V AC power supply and is fuse protected with max 6 A. All other connections are made according to the wiring diagram for the product that KSP is to be connected to, see KZP or KZM.

Electrical data
Supply voltage
24V AC -10% +15%, 50Hz

Power consumption

 

10 mA
Ambient temperature:
0°C -+50°CC
Operation
0°C -+70°C
Storage
-10°C -+70°C
Material
Transparent plastic
Enclosure class
lP 54
Measurement range
0-300 Pa
Accuracy
±0,6 Pa
Output voltage range
2-10 V DC
Maximum amperage
2 mA
Accuracy
±0,2 V


Figure 5.Wiring diagram.


DIMENSIONS AND WEIGHT
Size
ØD
A
Weight
160
159
100
0,9
200
199
95
1,1
250
249
89
1,3
315
314
80
1,5
400
399
68
1,9
500
499
50
2,2


Figure 6. The pressure hose is connected to (1) with supply air and (2) with exhaust air.


ORDER KEY

Product designation

Pressure sensor circular ducts

KSPa 1
-bbb

Size:
160, 200, 250, 315, 400, 500

Pressure sensor rectangular ducts
KSPa 2


SPECIFICATION EXAMPLE
GP XX
Swegon electronic pressure sensor type KSPa which is included in the e.r.i.c. system with the following functions:
  • Pressure measurement within 5-300
  • Static non fouling pressure measurement
  • Pressure shock-proof


Type:

KSPa 1-200
KSPa 2

xx items
xx items


Registered design. The company reserves the right to make design changes without prior notice.


   

Swegon Worldwide
Austria Belgium Czech Republic Denmark Finland France Germany Hungary Italy Netherlands
Norway Poland Slovak Republic Spain Sweden Switzerland United Arab Emirates United Kingdom United States of America
Partners
Belarus Bosnia-Herzegovina Croatia Estonia Greece Iceland Israel Latvia Lithuania Portugal
Romania Russia Serbia Slovenia - air handling units Turkey Ukraine